def add_machine():
     psspy.plant_data(busno, intgar1=ireg)
     psspy.machine_data_2(busno,
                          str(genid),
                          intgar1=int(status),
                          realar1=pgen,
                          realar3=Qlimit,
                          realar4=-Qlimit,
                          realar5=pmax)
Beispiel #2
0
 def get_mvar(i):
     """
     Changes the voltage set point at the synchronous machine
     solves the case
     returns the the new reactive power output of the sync machine.
     """
     psspy.plant_data(busno, realar1=i)
     ierr = psspy.fnsl()
     val = psspy.solved()
     if val == 0:
         ierr, mvar = psspy.macdat(busno, str(genid), 'Q')
         return mvar
     else:
         return None
def add_new_gen(gen_bus, P_inj, Q_max, Q_min):
    psspy.bus_data_3(gen_bus, [1, 1, 1, 1],
                     [0.0, 1.0, 0.0, 1.1, 0.9, 1.1, 0.9], "")
    psspy.bus_chng_3(gen_bus, [2, _i, _i, _i], [_f, _f, _f, _f, _f, _f, _f],
                     _s)
    psspy.plant_data(gen_bus, 0, [1.0, 100.0])
    psspy.machine_data_2(gen_bus, r"""1""", [1, 1, 0, 0, 0, 0], [
        0.0, 0.0, 9999.0, -9999.0, 9999.0, -9999.0, 100.0, 0.0, 1.0, 0.0, 0.0,
        1.0, 1.0, 1.0, 1.0, 1.0, 1.0
    ])
    psspy.machine_chng_2(gen_bus, r"""1""", [_i, _i, _i, _i, _i, 1], [
        P_inj, _f, Q_max, Q_min, P_inj, 0.0, _f, _f, _f, _f, _f, _f, _f, _f,
        _f, _f, _f
    ])

    return
# chang: this is wrong, each cluster has only ~120MVA capacity. I guess the power flow does not converge.

overloop = 0
# add this line.

Capacitor = 0
# capacitor

for temperature in [40, 50]:
    for terminalv in [0.9, 1.0, 1.1]:
        if temperature == 50:
            derate = 0.9
        else:
            derate = 1.0

        psspy.plant_data(600, _i, [terminalv, _f])

        for P_Gen in numpy.arange(0, S * derate + 0.01, 1):
            psspy.read(0, GridInfoPath + PowerFlowFileName)
            #psspy.switched_shunt_chng_3(104, [_i, _i, _i, _i, _i, _i, _i, _i, _i, _i, _i, _i],
            #                            [_f, _f, _f, _f, _f, _f, _f, _f, _f, _f, 0, _f], "")
            #psspy.switched_shunt_chng_3(204, [_i, _i, _i, _i, _i, _i, _i, _i, _i, _i, _i, _i],
            #                            [_f, _f, _f, _f, _f, _f, _f, _f, _f, _f, 0, _f], "")
            Q_Gen = max(-S * 0.6,
                        -math.sqrt(S * S * derate * derate - P_Gen * P_Gen))
            psspy.machine_data_2(101, r"""1""", [_i, _i, _i, _i, _i, _i], [
                P_Gen, Q_Gen, Q_Gen, Q_Gen, S, 0, _f, _f, _f, _f, _f, _f, _f,
                _f, _f, _f, _f
            ])
            psspy.machine_data_2(102, r"""1""", [_i, _i, _i, _i, _i, _i], [
                P_Gen, Q_Gen, Q_Gen, Q_Gen, S, 0, _f, _f, _f, _f, _f, _f, _f,
Beispiel #5
0
def preprocesado(parametros, info_casos):

   # se inicia el PSS/E
   initpss.inicia_psse(print_alert_psse=True)

   for x in info_casos:
      try:
         #se encuentra caso en la carpeta y se carga
         path_caso_psse = os.path.join(Rutas().ruta_casos, str(x.N_Caso) + '.sav')
         caso_pss = redpsse.CasoPSSE(filepath=path_caso_psse)
         caso_pss.load(save_previous=False)
         #se comprueba si el caso es peninsular o insular consultando las areas
         areas = redpsse.get_areas()
         area_numbers = []
         for a in areas:
            area_numbers.append(a.number)
         if 9 in area_numbers:
            Umin = parametros.U_min_i
            Umax = parametros.U_max_i
         else:
            Umin = parametros.U_min_p
            Umax = parametros.U_max_p
      except Exception as e:
         raise StandardError('Error al cargar el caso de referencia: {}'.format(e.message))

      try:
         # Cambio a tipo 2 los buses tipo 1 e incluyo generador con Pgen=0.01 MW
         # se recupera lista con buses tipo 1
         list_bus = redpsse.get_bus_number_used_by_tension_tipo(Umin=Umin, Umax=Umax, tipo=1)
         for bus_num in list_bus:
            # se modifica el tipo del bus
            ierr = psspy.bus_chng_3(bus_num, [2, _i, _i, _i], [_f, _f, _f, _f, _f, _f, _f], _s)
            # se crea una planta en el bus para poder añadir después el generador
            ierr = psspy.plant_data(bus_num, _i, [_f, _f])
            # se crea el generador con Pgen=0.01 MW
            intgar = [_i, _i, _i, _i, _i]
            Pgen = 0.01  # MW
            Qmin = 0  # MVar
            Qmax = 0  # MVar
            realar = [Pgen, _f, Qmin, Qmax, _f, _f, _f, _f, _f, _f, _f, _f, _f, _f, _f, _f]
            idn = str(11)
            ierr = psspy.machine_data_2(bus_num, idn, intgar, realar)
      except Exception as e:
         raise StandardError('Error al modificar los nudos en el caso de referencia: {}'.format(e.message))

      try:
         # Modificacion del rateA y rateB segun ficheros de entrada
         #se recupera una lista con ramas
         list_branches = redpsse.get_branch_list()
         for branch in list_branches:
            ibus = branch.from_bus
            jbus = branch.to_bus
            ckt= branch.idn
            #se calculan los nuevos rates A y B de la rama segun parametros de entrada
            rateA=parametros.Rate_A/100 * branch.rate_a
            rateB=parametros.Rate_B/100 * branch.rate_a
            intgar=[_i,_i,_i,_i,_i,_i]
            realar=[_f,_f,_f,rateA,rateB,_f,_f,_f,_f,_f,_f,_f,_f,_f,_f]
            #se modifica la rama con los nuevos rates A y B
            ierr = psspy.branch_data(ibus, jbus, ckt, intgar, realar)
      except Exception as e:
         raise StandardError('Error al modificar los rates A y B de las ramas en el caso de referencia: {}'.format(e.message))

      #se guarda temporalmente el caso procesado
      ierr = psspy.save(os.path.join(Rutas().ruta_casos_procesados, str(x.N_Caso) + '_procesado.sav'))
    PgenNOW = ppoc
    while abs(dPpoc) > PQMisMatch_Tol:
        PgenNOW = PgenNOW-dPpoc/P_factor
        QpocNOW = qpoc * 1.01 + 0.1
        dQpoc = QpocNOW - qpoc
        QgenNOW = QgenINImax[caseIndex]
        while abs(dQpoc) > PQMisMatch_Tol:
            QgenNOW = QgenNOW - dQpoc / Q_factor
            psspy.machine_data_2(bus_gen, '1', realar1=PgenNOW, realar2=QgenNOW, realar3=QgenNOW, realar4=QgenNOW)
            psspy.fdns([1, 0, 1, 1, 0, 0, 99, 0])
            ierr, Vinf = psspy.busdat(bus_inf, 'PU')
            ierr, Vpoc = psspy.busdat(bus_poc, 'PU')
            dV_POC = POC_VCtrl_Tgt - Vpoc
            while abs(dV_POC) > Vinf_MisMatch_Tol:
                Vsch = Vinf + dV_POC / V_factor
                psspy.plant_data(bus_inf, realar1=Vsch)  # set the infinite bus scheduled voltage to the estimated voltage for this condition
                psspy.fdns([0, 0, 1, 1, 0, 0, 99, 0])
                ierr, Vinf = psspy.busdat(bus_inf, 'PU')
                ierr, Vpoc = psspy.busdat(bus_poc, 'PU')
                dV_POC = POC_VCtrl_Tgt - Vpoc
            ierr, QpocNOW = psspy.brnmsc(bus_poc, bus_dummy, "1", 'Q')
            dQpoc = QpocNOW-qpoc
        ierr, PpocNOW = psspy.brnmsc(bus_poc, bus_dummy, "1", 'P')
        dPpoc = PpocNOW - ppoc
        print(dPpoc)
    psspy.machine_data_2(bus_gen, '1', realar1=PgenNOW, realar2=QgenNOW, realar3=QgenNOW, realar4=QgenNOW)
    ierr, PpocNOW = psspy.brnmsc(bus_poc, bus_dummy, "1", 'P')
    ierr, QpocNOW = psspy.brnmsc(bus_poc, bus_dummy, "1", 'Q')

    print "Line Flow_at_PoC (P) is %s" % PpocNOW
    print "Line Flow_at_PoC (Q) is %s" % QpocNOW
    # OPEN PSSE
    _i = psspy.getdefaultint()
    _f = psspy.getdefaultreal()
    _s = psspy.getdefaultchar()
    redirect.psse2py()
    psspy.psseinit(50000)

    FileName = f_list[case[test - 1]-1]
    psspy.case(CasePath + FileName)
    psspy.resq(CasePath + "Tamworth_SMIB.seq")
    psspy.addmodellibrary(CasePath + 'SMASC_E161_SMAPPC_E130_342_IVF150.dll')
    psspy.dyre_new([1, 1, 1, 1], CasePath + "Tamworth_SMIB_E161_E130.dyr", '', '', '')
    psspy.branch_data(bus_flt, bus_inf, '1', realar1=0, realar2=0.0001)
    ierr, line_rx = psspy.brndt2(bus_flt, bus_inf, '1', 'RX')
    psspy.ltap(bus_flt, bus_inf, r"""1""", 0.0001, bus_IDTRF, r"""IDTRF""", _f)
    psspy.plant_data(bus_inf, realar1=1.0)
    psspy.purgbrn(bus_IDTRF, bus_flt, r"""1""")
    psspy.two_winding_data_3(bus_flt, bus_IDTRF, r"""1""",
                             [1, bus_flt, 1, 0, 0, 0, 33, 0, bus_flt, 0, 1, 0, 1, 1, 1],
                             [0.0, 0.0001, 100.0, 1.0, 0.0, 0.0, 1.0, 0.0, 0.0, 0.0, 0.0, 1.0, 1.0, 1.0, 1.0, 0.0,
                              0.0, 1.1, 0.9, 1.1, 0.9, 0.0, 0.0, 0.0], r"""IDTRF""")

    OutputFilePath = FigurePath + '07. Grid Voltage Step Test' + "\\" + 'Test' + str(
        test+42) + '_' + FileName + '_sFac' + str(acceleration) + '_dT' + str(
        integration_step) + '_Grid Voltage Step Test.out'
    # ! Setup Dynamic Simulation parameters
    psspy.dynamics_solution_param_2([n_iteration, _i, _i, _i, _i, _i, _i, _i],
                                    [acceleration, tolerance, integration_step, _f, _f, _f, _f, _f])
    psspy.fdns([0, 0, 1, 1, 0, 0, 99, 0])

    # convert load , do not change
Beispiel #8
0
    results.append(min(results12))
    results.append(max_voltages(results13))
    results.append(min(results13))
    results.append(max_voltages(res_66kV))
    results.append(min(res_66kV))
    results.append(max_voltages(res_WT))
    results.append(min(res_WT))
    results.append(max_q(q_wt))
    results.append(min(q_wt))
    results.append(Qstat)
    results.append(Converged)
    result_dict[k] = results


################################ Energize#######################################################
psspy.plant_data(POI_bus, 0, [V_POI, 100.0])

# Fix WT voltage at 1.00 pu and set at 0 MW, 0 MVAr
for i in range(len(WT_num)):
    psspy.plant_data(WT_bus[i], 0, [1.00, 100.0])
    psspy.machine_chng_2(
        WT_bus[i], r"""1""", [1, _i, _i, _i, _i, _i],
        [0.0, 0.0, _f, _f, _f, _f, _f, _f, _f, _f, _f, _f, _f, _f, _f, _f, _f])
    psspy.fdns([0, 0, 0, 1, 1, 0, 0, 0])
    psspy.fdns([0, 0, 0, 1, 1, 0, 0, 0])

# 1
# Reconnect onshore bus HV
for i in range(num_groups):
    psspy.recn(ONSS_HV[i])
    # Auto-adjustment of taps is disabled
Beispiel #9
0
Tr_ONS_1 = []
Tr_ONS_2 = []
Tr_OFS_1 = []
Tr_OFS_2 = []
Qs_WTs_min = [] # UPDATE_Q_WT
Qs_WTs_max = [] # UPDATE_Q_WT

Num_Reactors = []
Convergence_test = []

ONS_TF = [] #UPDATE_XFO_LOADING
OFS_TF = [] #UPDATE_XFO_LOADING


# switch off shunts initially
psspy.plant_data(POI_bus,0,[V_POI, 100.0])
for i_sh in range (1,num_shunt+1):
    psspy.shunt_chng(ons_reac1_bus,str(i_sh),0,[_f,_f]) 
    psspy.shunt_chng(ons_reac2_bus,str(i_sh),0,[_f,_f]) 
    psspy.fdns([1,0,0,1,1,0,0,0])
    psspy.fdns([1,0,0,1,1,0,0,0])


psspy.plant_data(statcom1_bus,_i,[Vset_STAT,_f])
psspy.plant_data(statcom2_bus,_i,[Vset_STAT,_f])
# psspy.plant_data(128,_i,[Vset_STAT,_f])

psspy.fdns([1,0,0,1,1,0,0,0])
psspy.fdns([1,0,0,1,1,0,0,0])