Ejemplo n.º 1
0
def convert_to_pm_structure(net, opf_flow_lim="S"):
    net["OPF_converged"] = False
    net["converged"] = False
    _add_auxiliary_elements(net)
    init_results(net)
    ppc, ppci = _pd2ppc(net)
    ppci = build_ne_branch(net, ppci)
    net["_ppc_opf"] = ppci
    pm = ppc_to_pm(net, ppci)
    pm = add_pm_options(pm, net)
    net._pm = pm
    return net, pm, ppc, ppci
Ejemplo n.º 2
0
def _powerflow(net, **kwargs):
    """
    Gets called by runpp or rundcpp with different arguments.
    """

    # get infos from options
    ac = net["_options"]["ac"]
    algorithm = net["_options"]["algorithm"]

    net["converged"] = False
    net["OPF_converged"] = False
    _add_auxiliary_elements(net)

    if not ac or net["_options"]["init_results"]:
        verify_results(net)
    else:
        init_results(net)

    if net["_options"]["voltage_depend_loads"] and algorithm not in [
            'nr', 'bfsw'
    ] and not (allclose(net.load.const_z_percent.values, 0)
               and allclose(net.load.const_i_percent.values, 0)):
        logger.error((
            "pandapower powerflow does not support voltage depend loads for algorithm "
            "'%s'!") % algorithm)

    # clear lookups
    net._pd2ppc_lookups = {
        "bus": array([], dtype=int),
        "ext_grid": array([], dtype=int),
        "gen": array([], dtype=int),
        "branch": array([], dtype=int)
    }

    # convert pandapower net to ppc
    ppc, ppci = _pd2ppc(net)

    # store variables
    net["_ppc"] = ppc

    if "VERBOSE" not in kwargs:
        kwargs["VERBOSE"] = 0

    # ----- run the powerflow -----
    result = _run_pf_algorithm(ppci, net["_options"], **kwargs)
    # read the results (=ppci with results) to net
    _ppci_to_net(result, net)
Ejemplo n.º 3
0
def _extract_result_ppci_to_pp(net, ppc, ppci):
    # convert to pandapower indices
    ppc = _copy_results_ppci_to_ppc(ppci, ppc, mode="se")

    # inits empty result tables
    init_results(net, mode="se")

    # writes res_bus.vm_pu / va_degree and branch res
    _extract_results_se(net, ppc)

    # additionally, write bus power demand results (these are not written in _extract_results)
    mapping_table = net["_pd2ppc_lookups"]["bus"]
    net.res_bus_est.index = net.bus.index
    net.res_bus_est.p_mw = get_values(ppc["bus"][:, 2], net.bus.index.values,
                                      mapping_table)
    net.res_bus_est.q_mvar = get_values(ppc["bus"][:, 3], net.bus.index.values,
                                        mapping_table)
    return net
Ejemplo n.º 4
0
def _powerflow(net, **kwargs):
    """
    Gets called by runpp or rundcpp with different arguments.
    """

    # get infos from options
    ac = net["_options"]["ac"]
    algorithm = net["_options"]["algorithm"]

    net["converged"] = False
    net["OPF_converged"] = False
    _add_auxiliary_elements(net)

    if not ac or net["_options"]["init_results"]:
        verify_results(net)
    else:
        init_results(net)

    # TODO remove this when zip loads are integrated for all PF algorithms
    if algorithm not in ['nr', 'bfsw']:
        net["_options"]["voltage_depend_loads"] = False

    # clear lookups
    net._pd2ppc_lookups = {
        "bus": array([], dtype=int),
        "ext_grid": array([], dtype=int),
        "gen": array([], dtype=int),
        "branch": array([], dtype=int)
    }

    # convert pandapower net to ppc
    ppc, ppci = _pd2ppc(net)

    # store variables
    net["_ppc"] = ppc

    if not "VERBOSE" in kwargs:
        kwargs["VERBOSE"] = 0

    # ----- run the powerflow -----
    result = _run_pf_algorithm(ppci, net["_options"], **kwargs)
    # read the results (=ppci with results) to net
    _ppci_to_net(result, net)
Ejemplo n.º 5
0
def convert_to_pm_structure(net, opf_flow_lim="S"):
    if net["_options"]["voltage_depend_loads"] and not (
            np.allclose(net.load.const_z_percent.values, 0)
            and np.allclose(net.load.const_i_percent.values, 0)):
        logger.error(
            "pandapower optimal_powerflow does not support voltage depend loads."
        )
    net["OPF_converged"] = False
    net["converged"] = False
    _add_auxiliary_elements(net)
    init_results(net)
    ppc, ppci = _pd2ppc(net)
    ppci = build_ne_branch(net, ppci)
    net["_ppc_opf"] = ppci
    pm = ppc_to_pm(net, ppci)
    pm = add_pm_options(pm, net)
    pm = add_params_to_pm(net, pm)
    net._pm = pm
    return net, pm, ppc, ppci
Ejemplo n.º 6
0
                     recycle=None)
    _add_sc_options(net,
                    fault=fault,
                    case=case,
                    lv_tol_percent=lv_tol_percent,
                    tk_s=tk_s,
                    topology=topology,
                    r_fault_ohm=r_fault_ohm,
                    kappa_method=kappa_method,
                    x_fault_ohm=x_fault_ohm,
                    kappa=kappa,
                    ip=ip,
                    ith=ith,
                    branch_results=branch_results,
                    return_all_currents=return_all_currents)
    init_results(net, "sc")
    if fault == "3ph":
        _calc_sc(net)
    if fault == "2ph":
        _calc_sc(net)
    if fault == "1ph":
        _calc_sc_1ph(net)


def calc_single_sc(net,
                   bus,
                   fault="3ph",
                   case='max',
                   lv_tol_percent=10,
                   check_connectivity=True):
    """
Ejemplo n.º 7
0
def _optimal_powerflow(net, verbose, suppress_warnings, **kwargs):
    ac = net["_options"]["ac"]
    init = net["_options"]["init"]

    ppopt = ppoption(VERBOSE=verbose,
                     OPF_FLOW_LIM=2,
                     PF_DC=not ac,
                     INIT=init,
                     **kwargs)
    net["OPF_converged"] = False
    net["converged"] = False
    _add_auxiliary_elements(net)
    init_results(net, "opf")

    ppc, ppci = _pd2ppc(net)

    if not ac:
        ppci["bus"][:, VM] = 1.0
    net["_ppc_opf"] = ppci
    if len(net.dcline) > 0:
        ppci = add_userfcn(ppci,
                           'formulation',
                           _add_dcline_constraints,
                           args=net)

    if init == "pf":
        ppci = _run_pf_before_opf(net, ppci)
    if suppress_warnings:
        with warnings.catch_warnings():
            warnings.simplefilter("ignore")
            result = opf(ppci, ppopt)
    else:
        result = opf(ppci, ppopt)


#    net["_ppc_opf"] = result

    if verbose:
        ppopt['OUT_ALL'] = 1
        printpf(baseMVA=result["baseMVA"],
                bus=result["bus"],
                gen=result["gen"],
                fd=stdout,
                branch=result["branch"],
                success=result["success"],
                et=result["et"],
                ppopt=ppopt)

    if verbose:
        ppopt['OUT_ALL'] = 1
        printpf(baseMVA=result["baseMVA"],
                bus=result["bus"],
                gen=result["gen"],
                fd=stdout,
                branch=result["branch"],
                success=result["success"],
                et=result["et"],
                ppopt=ppopt)

    if not result["success"]:
        raise OPFNotConverged("Optimal Power Flow did not converge!")

    # ppci doesn't contain out of service elements, but ppc does -> copy results accordingly
    mode = net["_options"]["mode"]
    result = _copy_results_ppci_to_ppc(result, ppc, mode=mode)

    #    net["_ppc_opf"] = result
    net["OPF_converged"] = True
    _extract_results(net, result)
    _clean_up(net)
Ejemplo n.º 8
0
def runpp_3ph(net,
              calculate_voltage_angles=True,
              init="auto",
              max_iteration="auto",
              tolerance_mva=1e-8,
              trafo_model='t',
              trafo_loading="current",
              enforce_q_lims=False,
              numba=True,
              recycle=None,
              check_connectivity=True,
              switch_rx_ratio=2.0,
              delta_q=0,
              v_debug=False,
              **kwargs):
    """
 runpp_3ph: Performs Unbalanced/Asymmetric/Three Phase Load flow

    INPUT:
        **net** - The pandapower format network

    OPTIONAL:
        **algorithm** (str, "nr") - algorithm that is used to solve the power
        flow problem.

            The following algorithms are available:

                - "nr" Newton-Raphson (pypower implementation with numba accelerations)

                Used only for positive sequence network

                Zero and Negative sequence networks use Current Injection method

                Vnew = Y.inv * Ispecified ( from s_abc/v_abc old)

                Icalculated = Y * Vnew


        **calculate_voltage_angles** (bool, "auto") - consider voltage angles
        in loadflow calculation

            If True, voltage angles of ext_grids and transformer shifts are
            considered in the loadflow calculation. Considering the voltage
            angles is only necessary in meshed networks that are usually
            found in higher voltage levels. calculate_voltage_angles
            in "auto" mode defaults to:

                - True, if the network voltage level is above 70 kV
                - False otherwise

            The network voltage level is defined as the maximum rated voltage
            of any bus in the network that is connected to a line.


        **max_iteration** (int, "auto") - maximum number of iterations carried
        out in the power flow algorithm.

            In "auto" mode, the default value depends on the power flow solver:

                - 10 for "nr"

            For three phase calculations, its extended to 3 * max_iteration

        **tolerance_mva** (float, 1e-8) - loadflow termination condition
        referring to P / Q mismatch of node power in MVA

        **trafo_model**

            - transformer equivalent models
            - "t" - transformer is modeled as equivalent with the T-model.
            - "pi" - This is not recommended, since it is less exact than the T-model. So, for three phase load flow, its not implemented


        **trafo_loading** (str, "current") - mode of calculation for
        transformer loading

            Transformer loading can be calculated relative to the rated
            current or the rated power. In both cases the overall transformer
            loading is defined as the maximum loading on the two sides of
            the transformer.

            - "current"- transformer loading is given as ratio of current
                        flow and rated current of the transformer. This is the recommended
                        setting, since thermal as well as magnetic effects in the
                        transformer depend on the current.
            - "power" - transformer loading is given as ratio of apparent
                        power flow to the rated apparent power of the transformer.

        **enforce_q_lims** (bool, False) (Not tested with 3 Phase load flow)
        - respect generator reactive power limits

            If True, the reactive power limits in net.gen.max_q_mvar/min_q_mvar
            are respected in the loadflow. This is done by running a second
            loadflow if reactive power limits are violated at any generator,
            so that the runtime for the loadflow will increase if reactive
            power has to be curtailed.

            Note: enforce_q_lims only works if algorithm="nr"!


        **check_connectivity** (bool, True) - Perform an extra connectivity
        test after the conversion from pandapower to PYPOWER.

            If True, an extra connectivity test based on SciPy Compressed
            Sparse Graph Routines is perfomed. If check finds unsupplied buses,
            they are set out of service in the ppc

        **voltage_depend_loads** (bool, True)
        (Not tested with 3 Phase load flow) - consideration of voltage-dependent loads.

            If False, ``net.load.const_z_percent`` and ``net.load.const_i_percent``
            are not considered, i.e. ``net.load.p_mw`` and ``net.load.q_mvar``
            are considered as constant-power loads.

        **consider_line_temperature** (bool, False) (Not tested with 3 Phase
        load flow) - adjustment of line impedance based on provided line temperature.

            If True, ``net.line`` must contain a column ``temperature_degree_celsius``.
            The temperature dependency coefficient alpha must be provided in
            the ``net.line.alpha`` column, otherwise the default value of 0.004 is used.


        **KWARGS**:

        **numba** (bool, True) - Activation of numba JIT compiler in the
        newton solver

            If set to True, the numba JIT compiler is used to generate
            matrices for the powerflow, which leads to significant speed
            improvements.

        **switch_rx_ratio** (float, 2)

        (Not tested with 3 Phase load flow)  - rx_ratio of bus-bus-switches.
        If impedance is zero, buses connected by a closed bus-bus switch
        are fused to model an ideal bus. Otherwise, they are modelled
        as branches with resistance defined as z_ohm column in switch
        table and this parameter

        **delta_q**

        (Not tested with 3 Phase load flow) - Reactive power tolerance for option "enforce_q_lims"
        in kvar - helps convergence in some cases.

        **trafo3w_losses**

        (Not tested with 3 Phase load flow) - defines where open loop losses of three-winding
        transformers are considered. Valid options are "hv", "mv", "lv"
        for HV/MV/LV side or "star" for the star point.

        **v_debug** (bool, False) (Not tested with 3 Phase load flow) - if True,
        voltage values in each newton-raphson iteration are logged in the ppc.

        **init_vm_pu** (string/float/array/Series, None) (Not tested with 3
        Phase load flow) - Allows to define initialization specifically for
        voltage magnitudes. Only works with ``init == "auto"``!

            - "auto": all buses are initialized with the mean value of all
              voltage controlled elements in the grid
            - "flat" for flat start from 1.0
            - "results": voltage magnitude vector is taken from result table
            - a float with which all voltage magnitudes are initialized
            - an iterable with a voltage magnitude value for each bus
              (length and order has to match with the buses in net.bus)
            - a pandas Series with a voltage magnitude value for each bus
              (indexes have to match the indexes in net.bus)

         **init_va_degree** (string/float/array/Series, None) (Not tested with
         3 Phase load flow) - Allows to define initialization specifically for voltage angles.
         Only works with ``init == "auto"``!

            - "auto": voltage angles are initialized from DC power flow
              if angles are calculated or as 0 otherwise
            - "dc": voltage angles are initialized from DC power flow
            - "flat" for flat start from 0
            - "results": voltage angle vector is taken from result table
            - a float with which all voltage angles are initialized
            - an iterable with a voltage angle value for each bus (length
              and order has to match with the buses in net.bus)
            - a pandas Series with a voltage angle value for each bus (indexes
              have to match the indexes in net.bus)

        **recycle** (dict, none) - Reuse of internal powerflow variables for
        time series calculation.

            Contains a dict with the following parameters:
            bus_pq: If True PQ values of buses are updated

            gen: If True Sbus and the gen table in the ppc are recalculated

            Ybus: If True the admittance matrix (Ybus, Yf, Yt) is taken from

            ppc["internal"] and not reconstructed

        **neglect_open_switch_branches** (bool, False)

        (Not tested with 3 Phase load flow) - If True no auxiliary
        buses are created for branches when switches are opened at the branch.
        Instead branches are set out of service

    SEE ALSO:
         pp.add_zero_impedance_parameters(net):
         To add zero sequence parameters into network from the standard type

    EXAMPLES:
        Use this module like this:

        .. code-block:: python

            from pandapower.pf.runpp_3ph import runpp_3ph
            runpp_3ph(net)

    NOTES:
        - Three phase load flow uses Sequence Frame for power flow solution.
        - Three phase system is modelled with earth return.
        - PH-E load type is called as wye since Neutral and Earth are considered same
        - This solver has proved successful only for Earthed transformers (i.e Dyn,Yyn,YNyn & Yzn vector groups)
    """
    # =============================================================================
    # pandapower settings
    # =============================================================================
    overrule_options = {}
    if "user_pf_options" in net.keys() and len(net.user_pf_options) > 0:
        passed_parameters = _passed_runpp_parameters(locals())
        overrule_options = {
            key: val
            for key, val in net.user_pf_options.items()
            if key not in passed_parameters.keys()
        }
    if numba:
        numba = _check_if_numba_is_installed(numba)

    ac = True
    mode = "pf_3ph"  # TODO: Make valid modes (pf, pf_3ph, se, etc.) available in seperate file (similar to idx_bus.py)
    #    v_debug = kwargs.get("v_debug", False)
    copy_constraints_to_ppc = False
    if trafo_model == 'pi':
        raise Not_implemented("Three phase Power Flow doesnot support pi model\
                                because of lack of accuracy")


#    if calculate_voltage_angles == "auto":
#        calculate_voltage_angles = False
#        hv_buses = np.where(net.bus.vn_kv.values > 70)[0]  # Todo: Where does that number come from?
#        if len(hv_buses) > 0:
#            line_buses = net.line[["from_bus", "to_bus"]].values.flatten()
#            if len(set(net.bus.index[hv_buses]) & set(line_buses)) > 0:
# scipy spsolve options in NR power flow
    use_umfpack = kwargs.get("use_umfpack", True)
    permc_spec = kwargs.get("permc_spec", None)
    calculate_voltage_angles = True
    if init == "results" and net.res_bus_3ph.empty:
        init = "auto"
    if init == "auto":
        init = "dc" if calculate_voltage_angles else "flat"
    default_max_iteration = {
        "nr": 10,
        "bfsw": 10,
        "gs": 10000,
        "fdxb": 30,
        "fdbx": 30
    }
    if max_iteration == "auto":
        max_iteration = default_max_iteration["nr"]

    neglect_open_switch_branches = kwargs.get("neglect_open_switch_branches",
                                              False)
    only_v_results = kwargs.get("only_v_results", False)
    net._options = {}
    _add_ppc_options(net, calculate_voltage_angles=calculate_voltage_angles,
                     trafo_model=trafo_model, check_connectivity=check_connectivity,
                     mode=mode, switch_rx_ratio=switch_rx_ratio,
                     init_vm_pu=init, init_va_degree=init,
                     enforce_q_lims=enforce_q_lims, recycle=None,
                     voltage_depend_loads=False, delta=delta_q,\
                     neglect_open_switch_branches=neglect_open_switch_branches
                     )
    _add_pf_options(net, tolerance_mva=tolerance_mva, trafo_loading=trafo_loading,
                    numba=numba, ac=ac, algorithm="nr", max_iteration=max_iteration,\
                    only_v_results=only_v_results,v_debug=v_debug, use_umfpack=use_umfpack,
                    permc_spec=permc_spec)
    net._options.update(overrule_options)
    _check_bus_index_and_print_warning_if_high(net)
    _check_gen_index_and_print_warning_if_high(net)
    # =========================================================================
    # pd2ppc conversion
    # =========================================================================
    _, ppci1 = _pd2ppc_recycle(net, 1, recycle=recycle)

    _, ppci2 = _pd2ppc_recycle(net, 2, recycle=recycle)
    gs_eg, bs_eg = _add_ext_grid_sc_impedance(net, ppci2)

    _, ppci0 = _pd2ppc_recycle(net, 0, recycle=recycle)

    _, bus0, gen0, branch0, _, _, _ = _get_pf_variables_from_ppci(ppci0)
    base_mva, bus1, gen1, branch1, sl_bus, _, pq_bus = _get_pf_variables_from_ppci(
        ppci1)
    _, bus2, gen2, branch2, _, _, _ = _get_pf_variables_from_ppci(ppci2)

    # initialize the results after the conversion to ppc is done, otherwise init=results does not work
    init_results(net, "pf_3ph")

    # =============================================================================
    #     P Q values aggragated and summed up for each bus to make s_abc matrix
    #     s_abc for wye connections ; s_abc_delta for delta connection
    # =============================================================================
    s_abc_delta, s_abc = _load_mapping(net, ppci1)
    # =========================================================================
    # Construct Sequence Frame Bus admittance matrices Ybus
    # =========================================================================

    ppci0, ppci1, ppci2, y_0_pu, y_1_pu, y_2_pu, y_0_f, y_1_f, _,\
        y_0_t, y_1_t, _ = _get_y_bus(ppci0, ppci1, ppci2, recycle)
    # =========================================================================
    # Initial voltage values
    # =========================================================================
    nb = ppci1["bus"].shape[0]

    # make sure flat start is always respected, even with other voltage data in recycled ppc
    if init == "flat":
        v_012_it = np.zeros((3, nb), dtype=np.complex128)
        v_012_it[1, :] = 1.0
    else:
        v_012_it = np.concatenate([
            np.array(ppc["bus"][:, VM] *
                     np.exp(1j * np.deg2rad(ppc["bus"][:, VA]))).reshape(
                         (1, nb)) for ppc in (ppci0, ppci1, ppci2)
        ],
                                  axis=0).astype(np.complex128)

    # For Delta transformation:
    # Voltage changed from line-earth to line-line using V_T
    # s_abc/v_abc will now give line-line currents. This is converted to line-earth
    # current using I-T
    v_del_xfmn = np.array([[1, -1, 0], [0, 1, -1], [-1, 0, 1]])
    i_del_xfmn = np.array([[1, 0, -1], [-1, 1, 0], [0, -1, 1]])
    v_abc_it = sequence_to_phase(v_012_it)

    # =========================================================================
    #             Iteration using Power mismatch criterion
    # =========================================================================
    outer_tolerance_mva = 3e-8
    count = 0
    s_mismatch = np.array([[True], [True]], dtype=bool)
    t0 = perf_counter()
    while (s_mismatch >
           outer_tolerance_mva).any() and count < 30 * max_iteration:
        # =====================================================================
        #     Voltages and Current transformation for PQ and Slack bus
        # =====================================================================
        s_abc_pu = -np.divide(s_abc, ppci1["baseMVA"])
        s_abc_delta_pu = -np.divide(s_abc_delta, ppci1["baseMVA"])

        i_abc_it_wye = (np.divide(s_abc_pu, v_abc_it)).conjugate()
        i_abc_it_delta = np.matmul(i_del_xfmn, (np.divide(
            s_abc_delta_pu, np.matmul(v_del_xfmn, v_abc_it))).conjugate())

        # For buses with both delta and wye loads we need to sum of their currents
        # to sum up the currents
        i_abc_it = i_abc_it_wye + i_abc_it_delta
        i012_it = phase_to_sequence(i_abc_it)
        v1_for_s1 = v_012_it[1, :]
        i1_for_s1 = -i012_it[1, :]
        v0_pu_it = X012_to_X0(v_012_it)
        v2_pu_it = X012_to_X2(v_012_it)
        i0_pu_it = X012_to_X0(i012_it)
        i2_pu_it = X012_to_X2(i012_it)
        s1 = np.multiply(v1_for_s1, i1_for_s1.conjugate())
        # =============================================================================
        # Current used to find S1 Positive sequence power
        # =============================================================================

        ppci1["bus"][pq_bus, PD] = np.real(s1[pq_bus]) * ppci1["baseMVA"]
        ppci1["bus"][pq_bus, QD] = np.imag(s1[pq_bus]) * ppci1["baseMVA"]
        # =============================================================================
        # Conduct Positive sequence power flow
        # =============================================================================
        _run_newton_raphson_pf(ppci1, net._options)
        # =============================================================================
        # Conduct Negative and Zero sequence power flow
        # =============================================================================
        v0_pu_it = V_from_I(y_0_pu, i0_pu_it)
        v2_pu_it = V_from_I(y_2_pu, i2_pu_it)
        # =============================================================================
        #    Evaluate Positive Sequence Power Mismatch
        # =============================================================================
        i1_from_v_it = I1_from_V012(v_012_it, y_1_pu).flatten()
        s_from_voltage = S_from_VI_elementwise(v1_for_s1, i1_from_v_it)
        v1_pu_it = V1_from_ppc(ppci1)

        v_012_new = combine_X012(v0_pu_it, v1_pu_it, v2_pu_it)

        s_mismatch = np.abs(
            np.abs(s1[pq_bus]) - np.abs(s_from_voltage[pq_bus]))
        v_012_it = v_012_new
        v_abc_it = sequence_to_phase(v_012_it)
        count += 1
    et = perf_counter() - t0
    success = (count < 30 * max_iteration)
    for ppc in [ppci0, ppci1, ppci2]:
        ppc["et"] = et
        ppc["success"] = success
    # TODO: Add reference to paper to explain the following steps
    # This is required since the ext_grid power results are not correct if its
    # not done
    ref, pv, pq = bustypes(ppci0["bus"], ppci0["gen"])
    ref_gens = ppci0["internal"]["ref_gens"]
    ppci0["bus"][ref, GS] -= gs_eg
    ppci0["bus"][ref, BS] -= bs_eg
    y_0_pu, y_0_f, y_0_t = makeYbus(ppci0["baseMVA"], ppci0["bus"],
                                    ppci0["branch"])
    # revert the change, otherwise repeated calculation with recycled elements will fail
    ppci0["bus"][ref, GS] += gs_eg
    ppci0["bus"][ref, BS] += bs_eg
    # Bus, Branch, and Gen  power values
    bus0, gen0, branch0 = pfsoln(base_mva, bus0, gen0, branch0, y_0_pu, y_0_f,
                                 y_0_t, v_012_it[0, :].flatten(), sl_bus,
                                 ref_gens)
    bus1, gen1, branch1 = pfsoln(base_mva, bus1, gen1, branch1, y_1_pu, y_1_f,
                                 y_1_t, v_012_it[1, :].flatten(), sl_bus,
                                 ref_gens)
    bus2, gen2, branch2 = pfsoln(base_mva, bus2, gen2, branch2, y_1_pu, y_1_f,
                                 y_1_t, v_012_it[2, :].flatten(), sl_bus,
                                 ref_gens)
    ppci0 = _store_results_from_pf_in_ppci(ppci0, bus0, gen0, branch0)
    ppci1 = _store_results_from_pf_in_ppci(ppci1, bus1, gen1, branch1)
    ppci2 = _store_results_from_pf_in_ppci(ppci2, bus2, gen2, branch2)
    i_012_res = _current_from_voltage_results(y_0_pu, y_1_pu, v_012_it)
    s_012_res = S_from_VI_elementwise(v_012_it, i_012_res) * ppci1["baseMVA"]
    eg_is_mask = net["_is_elements"]['ext_grid']
    ext_grid_lookup = net["_pd2ppc_lookups"]["ext_grid"]
    eg_is_idx = net["ext_grid"].index.values[eg_is_mask]
    eg_idx_ppc = ext_grid_lookup[eg_is_idx]
    """ # 2 ext_grids Fix: Instead of the generator index, bus indices of the generators are used"""
    eg_bus_idx_ppc = np.real(ppci1["gen"][eg_idx_ppc, GEN_BUS]).astype(int)

    ppci0["gen"][eg_idx_ppc, PG] = s_012_res[0, eg_bus_idx_ppc].real
    ppci1["gen"][eg_idx_ppc, PG] = s_012_res[1, eg_bus_idx_ppc].real
    ppci2["gen"][eg_idx_ppc, PG] = s_012_res[2, eg_bus_idx_ppc].real
    ppci0["gen"][eg_idx_ppc, QG] = s_012_res[0, eg_bus_idx_ppc].imag
    ppci1["gen"][eg_idx_ppc, QG] = s_012_res[1, eg_bus_idx_ppc].imag
    ppci2["gen"][eg_idx_ppc, QG] = s_012_res[2, eg_bus_idx_ppc].imag

    ppc0 = net["_ppc0"]
    ppc1 = net["_ppc1"]
    ppc2 = net["_ppc2"]

    # ppci doesn't contain out of service elements, but ppc does -> copy results accordingly
    ppc0 = _copy_results_ppci_to_ppc(ppci0, ppc0, mode=mode)
    ppc1 = _copy_results_ppci_to_ppc(ppci1, ppc1, mode=mode)
    ppc2 = _copy_results_ppci_to_ppc(ppci2, ppc2, mode=mode)

    _extract_results_3ph(net, ppc0, ppc1, ppc2)

    #    Raise error if PF was not successful. If DC -> success is always 1

    if not ppci0["success"]:
        net["converged"] = False
        _clean_up(net, res=False)
        raise LoadflowNotConverged("Power Flow {0} did not converge after\
                                {1} iterations!".format("nr", count))
    else:
        net["converged"] = True

    _clean_up(net)