if LoadScenario == "SummerPeakLoad":
        file_name = "SummerHi-20171219-153047-34-SystemNormal"
    if LoadScenario == "SummerLowLoad":
        file_name = "SummerLowNormal-20161225-040047"
    if LoadScenario == "SimplifiedSystem":
        file_name = "WISF_ADD"
    # start simulation
    OutputFilePath = ProgramPath + str(fault_type) + "SimulationOutput4.outx"
    TimeShift = 0
    psspy.case(GridInfoPath + file_name + ".sav")
    # psspy.rstr(GridInfoPath+file_name+".snp")
    psspy.resq(GridInfoPath + "/" + file_name + ".seq")
    psspy.dyre_new([1, 1, 1, 1], GridInfoPath + "/" + file_name + ".dyr", "",
                   "", "")
    psspy.addmodellibrary(HuaweiModelPath + 'HWS2000_psse34.dll')
    psspy.addmodellibrary(HuaweiModelPath + 'MOD_GPM_PPC_V13_34.dll')
    psspy.addmodellibrary(HuaweiModelPath + 'MOD_GPM_SB_V7.dll')
    psspy.dynamics_solution_param_2([_i, _i, _i, _i, _i, _i, _i, _i],
                                    [0.300, _f, 0.001, 0.004, _f, _f, _f, _f])
    psspy.machine_data_2(
        500, r"""1""", [_i, _i, _i, _i, _i, _i],
        [90, _f, _f, _f, 96.8, _f, _f, _f, _f, _f, _f, _f, _f, _f, _f, _f, _f])
    psspy.fnsl([0, 0, 0, 1, 1, 1, 99, 0])

    psspy.bus_frequency_channel([1, 1000], r"""System frequency""")
    psspy.voltage_channel([2, -1, -1, 500], r"""Inverter Voltage Mag.""")
    psspy.voltage_channel([3, -1, -1, 800], r"""WISF POC Voltage Mag.""")
    psspy.branch_p_and_q_channel([4, -1, -1, 800, 900], r"""1""",
                                 [r"""P Injection""", r"""Q Injection"""])
    ierr = psspy.machine_array_channel([6, 2, 500], r"""1""",
    _i = psspy.getdefaultint()
    _f = psspy.getdefaultreal()
    _s = psspy.getdefaultchar()
    redirect.psse2py()
    psspy.psseinit(50000)

    dVref = 0.05
    POC_VCtrl_Tgt = 1.00
    CON_PPCVref = 10
    VAR_PPCVini = 1

    FileName = f_list[case[test - 1] - 1]
    psspy.case(CasePath + FileName)
    psspy.resq(CasePath + "Tamworth_SMIB.seq")
    psspy.addmodellibrary(CasePath + 'SMASC_E161_SMAPPC_E130_342_IVF150.dll')
    psspy.dyre_new([1, 1, 1, 1], CasePath + "Tamworth_SMIB_E161_E130.dyr", '',
                   '', '')

    OutputFilePath = FigurePath + '05. PoC Vref Step Test' + "\\" + 'Test' + str(
        test +
        18) + '_' + FileName + '_sFac' + str(acceleration) + '_dT' + str(
            integration_step) + '_PoC Vref Step Test.out'
    # Setup Dynamic Simulation parameters
    psspy.dynamics_solution_param_2(
        [n_iteration, _i, _i, _i, _i, _i, _i, _i],
        [acceleration, tolerance, integration_step, _f, _f, _f, _f, _f])
    psspy.fdns([0, 0, 1, 1, 0, 0, 99, 0])

    # convert load , do not change
    psspy.cong(0)
Example #3
0
    file_name = "NEOEN Western Downs Solar Farm_C3WV_mod"

#########################################   Read Input List #######################################

# Active Power Setpoint
ActivePowerSetpoint = range(0, 101, 50)
ReactivePowerSetpoint = [-40, 40]
vref = numpy.arange(0.70, 1.3, 0.05)
S = 100
# Initialize
psspy.read(0, GridInfoPath + LoadScenario + "/" + file_name + ".raw")
psspy.resq(GridInfoPath + LoadScenario + "/" + file_name + ".seq")
psspy.dyre_new([1, 1, 1, 1],
               GridInfoPath + LoadScenario + "/" + file_name + ".dyr", "", "",
               "")
psspy.addmodellibrary(HuaweiModelPath + 'HWH9001_342.dll')
psspy.addmodellibrary(HuaweiModelPath +
                      'PPC_PSSE_ver_13_08_34_2_10082018_AUS.dll')
psspy.addmodellibrary(HuaweiModelPath + 'MOD_GPM_SB_V7.dll')
psspy.dynamics_solution_param_2([_i, _i, _i, _i, _i, _i, _i, _i],
                                [1.000, _f, 0.001, 0.004, _f, _f, _f, _f])

for i in range(0, len(ActivePowerSetpoint)):
    for j in range(0, len(ReactivePowerSetpoint)):
        for k in range(0, len(vref)):
            # re - initialize
            psspy.read(0,
                       GridInfoPath + LoadScenario + "/" + file_name + ".raw")
            psspy.resq(GridInfoPath + LoadScenario + "/" + file_name + ".seq")
            psspy.dyre_new([1, 1, 1, 1], GridInfoPath + LoadScenario + "/" +
                           file_name + ".dyr", "", "", "")
FigurePath = "C:/NEOEN/R_Results/"

if LoadScenario == "SummerPeakLoad":
    file_name = "SummerHi-20171219-153047-34-SystemNormal_all_bus_DDSF"
if LoadScenario == "SummerLowLoad":
    file_name = "SummerLo-20171226-043047-34-SystemNormal_all_bus_DDSF"
if LoadScenario == "SimplifiedSystem":
    file_name = "NEOEN Western Downs Solar Farm_C3WV_mod"

# Initialize
psspy.read(0, GridInfoPath + LoadScenario + "/" + file_name + ".raw")
psspy.resq(GridInfoPath + LoadScenario + "/" + file_name + ".seq")
psspy.dyre_new([1, 1, 1, 1],
               GridInfoPath + LoadScenario + "/" + file_name + ".dyr", "", "",
               "")
psspy.addmodellibrary(GridInfoPath + 'dsusr.dll')
psspy.addmodellibrary(HuaweiModelPath + 'HWH9001_342.dll')
psspy.addmodellibrary(HuaweiModelPath +
                      'PPC_PSSE_ver_13_08_34_2_10082018_AUS.dll')
psspy.addmodellibrary(HuaweiModelPath + 'MOD_GPM_SB_V7.dll')
psspy.addmodellibrary(GridInfoPath + 'GEWTG34.dll')
psspy.addmodellibrary(GridInfoPath + 'SMAPPC_B111_34_IVF111.dll')
psspy.addmodellibrary(GridInfoPath + 'SMASC_C135_34_IVF111.dll')
[ierr, var_ppc_conp] = psspy.mdlind(101, '1', 'EXC', 'CON')
[ierr, var_ppc_setp] = psspy.mdlind(101, '1', 'EXC', 'VAR')
[ierr, var_ppc_mode] = psspy.mdlind(101, '1', 'EXC', 'ICON')
[ierr, var_inv_con] = psspy.mdlind(101, '1', 'GEN', 'CON')
[ierr, var_inv_var] = psspy.mdlind(101, '1', 'GEN', 'VAR')
psspy.machine_data_2(101, r"""1""", [_i, _i, _i, _i, _i, _i], [
    ActivePowerSetpoint * S, _f, _f, _f, 120, _f, _f, _f, _f, _f, _f, _f, _f,
    _f, _f, _f, _f