コード例 #1
0
ファイル: test_basic.py プロジェクト: Bengt/GridCal
def test_basic():
    """
    Basic GridCal test, also useful for a basic tutorial. In this case the
    magnetizing branch of the transformers is neglected by inputting 1e-20
    excitation current and iron core losses.
    The results are identical to ETAP's, which always uses this assumption in
    balanced load flow calculations.
    """
    test_name = "test_basic"
    grid = MultiCircuit(name=test_name)
    S_base = 100  # MVA
    grid.Sbase = S_base
    grid.time_profile = None
    grid.logger = list()

    # Create buses
    POI = Bus(
        name="POI",
        vnom=100,  #kV
        is_slack=True)
    grid.add_bus(POI)

    B_C3 = Bus(name="B_C3", vnom=10)  #kV
    grid.add_bus(B_C3)

    B_MV_M32 = Bus(name="B_MV_M32", vnom=10)  #kV
    grid.add_bus(B_MV_M32)

    B_LV_M32 = Bus(name="B_LV_M32", vnom=0.6)  #kV
    grid.add_bus(B_LV_M32)

    # Create voltage controlled generators (or slack, a.k.a. swing)
    UT = Generator(name="Utility")
    UT.bus = POI
    grid.add_generator(POI, UT)

    # Create static generators (with fixed power factor)
    M32 = StaticGenerator(
        name="M32",
        P=4.2,  # MW
        Q=0.0j)  # MVAR
    M32.bus = B_LV_M32
    grid.add_static_generator(B_LV_M32, M32)

    # Create transformer types
    s = 5  # MVA
    z = 8  # %
    xr = 40
    SS = TransformerType(
        name="SS",
        hv_nominal_voltage=100,  # kV
        lv_nominal_voltage=10,  # kV
        nominal_power=s,
        copper_losses=complex_impedance(z, xr).real * s * 1000 / S_base,
        iron_losses=1e-20,
        no_load_current=1e-20,
        short_circuit_voltage=z)
    grid.add_transformer_type(SS)

    s = 5  # MVA
    z = 6  # %
    xr = 20
    PM = TransformerType(
        name="PM",
        hv_nominal_voltage=10,  # kV
        lv_nominal_voltage=0.6,  # kV
        nominal_power=s,
        copper_losses=complex_impedance(z, xr).real * s * 1000 / S_base,
        iron_losses=1e-20,
        no_load_current=1e-20,
        short_circuit_voltage=z)
    grid.add_transformer_type(PM)

    # Create branches
    X_C3 = Branch(bus_from=POI,
                  bus_to=B_C3,
                  name="X_C3",
                  branch_type=BranchType.Transformer,
                  template=SS)
    grid.add_branch(X_C3)

    C_M32 = Branch(bus_from=B_C3,
                   bus_to=B_MV_M32,
                   name="C_M32",
                   r=0.784,
                   x=0.174)
    grid.add_branch(C_M32)

    X_M32 = Branch(bus_from=B_MV_M32,
                   bus_to=B_LV_M32,
                   name="X_M32",
                   branch_type=BranchType.Transformer,
                   template=PM)
    grid.add_branch(X_M32)

    # Apply templates (device types)
    grid.apply_all_branch_types()

    print("Buses:")
    for i, b in enumerate(grid.buses):
        print(f" - bus[{i}]: {b}")
    print()

    options = PowerFlowOptions(SolverType.LM,
                               verbose=True,
                               initialize_with_existing_solution=True,
                               multi_core=True,
                               control_q=ReactivePowerControlMode.Direct,
                               tolerance=1e-6,
                               max_iter=99)

    power_flow = PowerFlow(grid, options)
    power_flow.run()

    approx_volt = [round(100 * abs(v), 1) for v in power_flow.results.voltage]
    solution = [
        100.0, 99.6, 102.7, 102.9
    ]  # Expected solution from GridCal and ETAP 16.1.0, for reference

    print()
    print(f"Test: {test_name}")
    print(f"Results:  {approx_volt}")
    print(f"Solution: {solution}")
    print()

    print("Generators:")
    for g in grid.get_generators():
        print(f" - Generator {g}: q_min={g.Qmin}pu, q_max={g.Qmax}pu")
    print()

    print("Branches:")
    for b in grid.branches:
        print(f" - {b}:")
        print(f"   R = {round(b.R, 4)} pu")
        print(f"   X = {round(b.X, 4)} pu")
        print(f"   X/R = {round(b.X/b.R, 1)}")
        print(f"   G = {round(b.G, 4)} pu")
        print(f"   B = {round(b.B, 4)} pu")
    print()

    print("Transformer types:")
    for t in grid.transformer_types:
        print(
            f" - {t}: Copper losses={int(t.Pcu)}kW, Iron losses={int(t.Pfe)}kW, SC voltage={t.Vsc}%"
        )
    print()

    print("Losses:")
    for i in range(len(grid.branches)):
        print(
            f" - {grid.branches[i]}: losses={1000*round(power_flow.results.losses[i], 3)} kVA"
        )
    print()

    equal = True
    for i in range(len(approx_volt)):
        if approx_volt[i] != solution[i]:
            equal = False

    assert equal
コード例 #2
0
def test_xfo_static_tap_3():
    """
    Basic test with the main transformer's  HV tap (X_C3) set at -2.5%
    (0.975 pu), which raises the LV by the same amount (+2.5%).
    """
    test_name = "test_xfo_static_tap_3"
    grid = MultiCircuit(name=test_name)
    grid.Sbase = Sbase
    grid.time_profile = None
    grid.logger = Logger()

    # Create buses
    POI = Bus(
        name="POI",
        vnom=100,  # kV
        is_slack=True)
    grid.add_bus(POI)

    B_C3 = Bus(name="B_C3", vnom=10)  # kV
    grid.add_bus(B_C3)

    B_MV_M32 = Bus(name="B_MV_M32", vnom=10)  # kV
    grid.add_bus(B_MV_M32)

    B_LV_M32 = Bus(name="B_LV_M32", vnom=0.6)  # kV
    grid.add_bus(B_LV_M32)

    # Create voltage controlled generators (or slack, a.k.a. swing)
    UT = Generator(name="Utility")
    UT.bus = POI
    grid.add_generator(POI, UT)

    # Create static generators (with fixed power factor)
    M32 = StaticGenerator(name="M32", P=4.2, Q=0.0)  # MVA (complex)
    M32.bus = B_LV_M32
    grid.add_static_generator(B_LV_M32, M32)

    # Create transformer types
    s = 5  # MVA
    z = 8  # %
    xr = 40
    SS = TransformerType(
        name="SS",
        hv_nominal_voltage=100,  # kV
        lv_nominal_voltage=10,  # kV
        nominal_power=s,
        copper_losses=complex_impedance(z, xr).real * s * 1000 / Sbase,
        iron_losses=6.25,  # kW
        no_load_current=0.5,  # %
        short_circuit_voltage=z)
    grid.add_transformer_type(SS)

    s = 5  # MVA
    z = 6  # %
    xr = 20
    PM = TransformerType(
        name="PM",
        hv_nominal_voltage=10,  # kV
        lv_nominal_voltage=0.6,  # kV
        nominal_power=s,
        copper_losses=complex_impedance(z, xr).real * s * 1000 / Sbase,
        iron_losses=6.25,  # kW
        no_load_current=0.5,  # %
        short_circuit_voltage=z)
    grid.add_transformer_type(PM)

    # Create branches
    X_C3 = Branch(bus_from=POI,
                  bus_to=B_C3,
                  name="X_C3",
                  branch_type=BranchType.Transformer,
                  template=SS,
                  tap=0.975)
    # update to a more precise tap changer
    X_C3.apply_tap_changer(
        TapChanger(taps_up=20, taps_down=20, max_reg=1.1, min_reg=0.9))
    grid.add_branch(X_C3)

    C_M32 = Branch(bus_from=B_C3,
                   bus_to=B_MV_M32,
                   name="C_M32",
                   r=0.784,
                   x=0.174)
    grid.add_branch(C_M32)

    X_M32 = Branch(bus_from=B_MV_M32,
                   bus_to=B_LV_M32,
                   name="X_M32",
                   branch_type=BranchType.Transformer,
                   template=PM)
    grid.add_branch(X_M32)

    # Apply templates (device types)
    grid.apply_all_branch_types()

    print("Buses:")
    for i, b in enumerate(grid.buses):
        print(f" - bus[{i}]: {b}")
    print()

    options = PowerFlowOptions(SolverType.NR,
                               verbose=True,
                               initialize_with_existing_solution=True,
                               multi_core=True,
                               control_q=ReactivePowerControlMode.Direct,
                               tolerance=1e-6,
                               max_iter=15)

    power_flow = PowerFlowDriver(grid, options)
    power_flow.run()

    print()
    print(f"Test: {test_name}")
    print()

    print("Generators:")
    for g in grid.get_generators():
        print(f" - Generator {g}: q_min={g.Qmin} MVAR, q_max={g.Qmax} MVAR")
    print()

    print("Branches:")
    for b in grid.branches:
        print(f" - {b}:")
        print(f"   R = {round(b.R, 4)} pu")
        print(f"   X = {round(b.X, 4)} pu")
        print(f"   X/R = {round(b.X/b.R, 1)}")
        print(f"   G = {round(b.G, 4)} pu")
        print(f"   B = {round(b.B, 4)} pu")
    print()

    print("Transformer types:")
    for t in grid.transformer_types:
        print(f" - {t}: Copper losses={int(t.Pcu)}kW, "
              f"Iron losses={int(t.Pfe)}kW, SC voltage={t.Vsc}%")
    print()

    print("Losses:")
    for i in range(len(grid.branches)):
        print(
            f" - {grid.branches[i]}: losses={1000*round(power_flow.results.losses[i], 3)} kVA"
        )
    print()

    equal = False
    for i, branch in enumerate(grid.branches):
        if branch.name == "X_C3":
            equal = power_flow.results.tap_module[i] == branch.tap_module

    if not equal:
        grid.export_pf(f"{test_name}_results.xlsx", power_flow.results)
        grid.save_excel(f"{test_name}_grid.xlsx")

    assert equal
コード例 #3
0
def test_xfo_static_tap_1():
    """
    Basic test with the main transformer's  HV tap (X_C3) set at +5% (1.05 pu),
    which lowers the LV by the same amount (-5%).
    """
    test_name = "test_xfo_static_tap_1"
    grid = MultiCircuit(name=test_name)
    grid.Sbase = Sbase
    grid.time_profile = None
    grid.logger = Logger()

    # Create buses
    POI = Bus(
        name="POI",
        vnom=100,  #kV
        is_slack=True)
    grid.add_bus(POI)

    B_C3 = Bus(name="B_C3", vnom=10)  #kV
    grid.add_bus(B_C3)

    B_MV_M32 = Bus(name="B_MV_M32", vnom=10)  #kV
    grid.add_bus(B_MV_M32)

    B_LV_M32 = Bus(name="B_LV_M32", vnom=0.6)  #kV
    grid.add_bus(B_LV_M32)

    # Create voltage controlled generators (or slack, a.k.a. swing)
    UT = Generator(name="Utility")
    UT.bus = POI
    grid.add_generator(POI, UT)

    # Create static generators (with fixed power factor)
    M32 = StaticGenerator(name="M32", P=4.2, Q=0.0)  # MVA (complex)
    M32.bus = B_LV_M32
    grid.add_static_generator(B_LV_M32, M32)

    # Create transformer types
    s = 5  # MVA
    z = 8  # %
    xr = 40
    SS = TransformerType(
        name="SS",
        hv_nominal_voltage=100,  # kV
        lv_nominal_voltage=10,  # kV
        nominal_power=s,
        copper_losses=complex_impedance(z, xr).real * s * 1000 / Sbase,
        iron_losses=6.25,  # kW
        no_load_current=0.5,  # %
        short_circuit_voltage=z)
    grid.add_transformer_type(SS)

    s = 5  # MVA
    z = 6  # %
    xr = 20
    PM = TransformerType(
        name="PM",
        hv_nominal_voltage=10,  # kV
        lv_nominal_voltage=0.6,  # kV
        nominal_power=s,
        copper_losses=complex_impedance(z, xr).real * s * 1000 / Sbase,
        iron_losses=6.25,  # kW
        no_load_current=0.5,  # %
        short_circuit_voltage=z)
    grid.add_transformer_type(PM)

    # Create branches
    X_C3 = Branch(bus_from=POI,
                  bus_to=B_C3,
                  name="X_C3",
                  branch_type=BranchType.Transformer,
                  template=SS,
                  tap=1.05)
    grid.add_branch(X_C3)

    C_M32 = Branch(bus_from=B_C3,
                   bus_to=B_MV_M32,
                   name="C_M32",
                   r=0.784,
                   x=0.174)
    grid.add_branch(C_M32)

    X_M32 = Branch(bus_from=B_MV_M32,
                   bus_to=B_LV_M32,
                   name="X_M32",
                   branch_type=BranchType.Transformer,
                   template=PM)
    grid.add_branch(X_M32)

    # Apply templates (device types)
    grid.apply_all_branch_types()

    print("Buses:")
    for i, b in enumerate(grid.buses):
        print(f" - bus[{i}]: {b}")
    print()

    options = PowerFlowOptions(SolverType.NR,
                               verbose=True,
                               initialize_with_existing_solution=True,
                               multi_core=True,
                               control_q=ReactivePowerControlMode.Direct,
                               tolerance=1e-6,
                               max_iter=99)

    power_flow = PowerFlowDriver(grid, options)
    power_flow.run()

    approx_volt = [round(100 * abs(v), 1) for v in power_flow.results.voltage]
    solution = [100.0, 94.7, 98.0, 98.1]  # Expected solution from GridCal

    print()
    print(f"Test: {test_name}")
    print(f"Results:  {approx_volt}")
    print(f"Solution: {solution}")
    print()

    print("Generators:")
    for g in grid.get_generators():
        print(f" - Generator {g}: q_min={g.Qmin} MVAR, q_max={g.Qmax} MVAR")
    print()

    print("Branches:")
    for b in grid.branches:
        print(f" - {b}:")
        print(f"   R = {round(b.R, 4)} pu")
        print(f"   X = {round(b.X, 4)} pu")
        print(f"   X/R = {round(b.X/b.R, 1)}")
        print(f"   G = {round(b.G, 4)} pu")
        print(f"   B = {round(b.B, 4)} pu")
    print()

    print("Transformer types:")
    for t in grid.transformer_types:
        print(
            f" - {t}: Copper losses={int(t.Pcu)}kW, Iron losses={int(t.Pfe)}kW, SC voltage={t.Vsc}%"
        )
    print()

    print("Losses:")
    for i in range(len(grid.branches)):
        print(
            f" - {grid.branches[i]}: losses={1000*round(power_flow.results.losses[i], 3)} kVA"
        )
    print()

    equal = True
    for i in range(len(approx_volt)):
        if approx_volt[i] != solution[i]:
            equal = False

    assert equal
コード例 #4
0
def test_gridcal_regulator():
    """
    GridCal test for the new implementation of transformer voltage regulators.
    """
    test_name = "test_gridcal_regulator"
    grid = MultiCircuit(name=test_name)
    grid.Sbase = 100.0  # MVA
    grid.time_profile = None
    grid.logger = Logger()

    # Create buses
    POI = Bus(
        name="POI",
        vnom=100,  # kV
        is_slack=True)
    grid.add_bus(POI)

    B_C3 = Bus(name="B_C3", vnom=10)  # kV
    grid.add_bus(B_C3)

    B_MV_M32 = Bus(name="B_MV_M32", vnom=10)  # kV
    grid.add_bus(B_MV_M32)

    B_LV_M32 = Bus(name="B_LV_M32", vnom=0.6)  # kV
    grid.add_bus(B_LV_M32)

    # Create voltage controlled generators (or slack, a.k.a. swing)
    UT = Generator(name="Utility")
    UT.bus = POI
    grid.add_generator(POI, UT)

    # Create static generators (with fixed power factor)
    M32 = StaticGenerator(name="M32", P=4.2, Q=0.0)  # MVA (complex)
    M32.bus = B_LV_M32
    grid.add_static_generator(B_LV_M32, M32)

    # Create transformer types
    s = 100  # MVA
    z = 8  # %
    xr = 40
    SS = TransformerType(
        name="SS",
        hv_nominal_voltage=100,  # kV
        lv_nominal_voltage=10,  # kV
        nominal_power=s,  # MVA
        copper_losses=complex_impedance(z, xr).real * s * 1000.0 /
        grid.Sbase,  # kW
        iron_losses=125,  # kW
        no_load_current=0.5,  # %
        short_circuit_voltage=z)  # %
    grid.add_transformer_type(SS)

    s = 5  # MVA
    z = 6  # %
    xr = 20
    PM = TransformerType(
        name="PM",
        hv_nominal_voltage=10,  # kV
        lv_nominal_voltage=0.6,  # kV
        nominal_power=s,  # MVA
        copper_losses=complex_impedance(z, xr).real * s * 1000.0 /
        grid.Sbase,  # kW
        iron_losses=6.25,  # kW
        no_load_current=0.5,  # %
        short_circuit_voltage=z)  # %
    grid.add_transformer_type(PM)

    # Create branches
    X_C3 = Branch(bus_from=POI,
                  bus_to=B_C3,
                  name="X_C3",
                  branch_type=BranchType.Transformer,
                  template=SS,
                  bus_to_regulated=True,
                  vset=1.05)
    X_C3.tap_changer = TapChanger(taps_up=16,
                                  taps_down=16,
                                  max_reg=1.1,
                                  min_reg=0.9)
    X_C3.tap_changer.set_tap(X_C3.tap_module)
    grid.add_branch(X_C3)

    C_M32 = Branch(bus_from=B_C3,
                   bus_to=B_MV_M32,
                   name="C_M32",
                   r=7.84,
                   x=1.74)
    grid.add_branch(C_M32)

    X_M32 = Branch(bus_from=B_MV_M32,
                   bus_to=B_LV_M32,
                   name="X_M32",
                   branch_type=BranchType.Transformer,
                   template=PM)
    grid.add_branch(X_M32)

    # Apply templates (device types)
    grid.apply_all_branch_types()

    print("Buses:")
    for i, b in enumerate(grid.buses):
        print(f" - bus[{i}]: {b}")
    print()

    options = PowerFlowOptions(SolverType.NR,
                               verbose=True,
                               initialize_with_existing_solution=True,
                               multi_core=True,
                               control_q=ReactivePowerControlMode.Direct,
                               control_taps=TapsControlMode.Direct,
                               tolerance=1e-6,
                               max_iter=99)

    power_flow = PowerFlowDriver(grid, options)
    power_flow.run()

    approx_volt = [round(100 * abs(v), 1) for v in power_flow.results.voltage]
    solution = [100.0, 105.2, 130.0, 130.1]  # Expected solution from GridCal

    print()
    print(f"Test: {test_name}")
    print(f"Results:  {approx_volt}")
    print(f"Solution: {solution}")
    print()

    print("Generators:")
    for g in grid.get_generators():
        print(f" - Generator {g}: q_min={g.Qmin}pu, q_max={g.Qmax}pu")
    print()

    print("Branches:")
    branches = grid.get_branches()
    for b in grid.transformers2w:
        print(
            f" - {b}: R={round(b.R, 4)}pu, X={round(b.X, 4)}pu, X/R={round(b.X/b.R, 1)}, vset={b.vset}"
        )
    print()

    print("Transformer types:")
    for t in grid.transformer_types:
        print(
            f" - {t}: Copper losses={int(t.Pcu)}kW, Iron losses={int(t.Pfe)}kW, SC voltage={t.Vsc}%"
        )
    print()

    print("Losses:")
    for i in range(len(branches)):
        print(
            f" - {branches[i]}: losses={round(power_flow.results.losses[i], 3)} MVA"
        )
    print()

    tr_vset = [tr.vset for tr in grid.transformers2w]
    print(f"Voltage settings: {tr_vset}")

    equal = np.isclose(approx_volt, solution, atol=1e-3).all()

    assert equal